H-1
Appendix H
WARNING: These circuits are
intended for 24 hour
alarm monitoring only.
UL 1076 requires a TSW-2 tamper switch as
well as a supervised printer (PAL-1/PAL-2).
Other supervised printers that are selectable
in CSG-M are the TI-820 and the LA-50.
Only Models TRI-60/-60D/-60R or TRI-B6/-
B6D/-B6R may be used as security points.
A COMMUNICATION FAILURE with a TRI
device configured for SECURITY results in
a SECURITY ALARM as well as a commu-
nication trouble. When installing a TRI
device in the CSG-M, be sure to set the
device usage field to security; otherwise,
the device usage defaults to fire alarm.
Installing A Security Point
CAUTION:
• When setting the device address using
the FPI-32, select the normally closed
alarm causing input.
• Connect only one switch per TRI input.
For proprietary burglary application
(UL 1076):
• Use a TSW-2 tamper switch to monitor
the main enclosure.
• Monitor each TRI-60/-60D/-60R or
TRI-B6/-B6D/-B6R related to this
application for 24 hours by using a
listed motion detector (to prevent
tampering).
Installing the Security Point for UL 1076
* END OF LINE DEVICE: P/N 140-820185
REFER TO ,
P/N 315-092329 OR 315-093315, AS APPLICABLE
TRI INSTALLATION INSTRUCTIONS
1 1 1
2 2 2
3 3 3
4 4 4
5 5 5
7 7 7
6 6 6
8 8 8
ANALOG
LOOP IN
ANALOG
LOOP IN
ANALOG
LOOP IN
SWITCH SWITCH SWITCH A
SWITCH B
NC NC NC
NC
++ +++ +
-- --- -
ANALOG
LOOP
OUT
ANALOG
LOOP
OUT
ANALOG
LOOP
OUT
EOL *
3.6K
1/4W
EOL *
3.6K
1/4W
EOL *
3.6K
1/4W
EOL *
3.6K
1/4W
GND GND GND
NOT USED
TRI-60 / TRI-B6 TRI-60R / TRI-B6R TRI-60D / TRI-B6D
NOT USED