Operation
Test: Pyro_diags
Use Test Pyro-diags to display a series of
statistics typically used by Siemens Indus-
try, Inc., to evaluate the operation of the
System. A special password is required for
access to this function.
Test: Pre_alarm
Use Test Pre_alarm to test pre-alarm logic.
From the Test menu, use the left or right
arrow key to cause the P in Pre_alarm to
start blinking:
TEST: PRE ALARM
The System asks you for a module number
and device number.
TYPE IN MODULE & DEVICE:
Type the three-digit module number and
the three-digit device number using the
numeric keypad and press ENTER.
The System then sends information to force
this detector into pre-alarm. Once it pre-
alarms, or after a delay, the MXL-IQ then
restores the detector to its proper pre-alarm
setting.
Test: ASD_Devices
Use Test ASD_Devices to disable ASD
parameters and allow timely response to
test gas.
From the Test menu, use the Left or Right
arrow key to cause the A in ASD_Devices
to start blinking.
(If you press HELP at this point, the system
displays:
TEST: ASD DETECTORS
Press HELP again to return to the Test
menu.)
Press ENTER to test the ASD devices
present in the system. The System dis-
plays:
TESTING OF ASD DEVICE ENABLED
Press the ENTER key again and the System
displays:
TESTING OF ASD DEVICE DISABLED
Press the ENTER key to toggle between
Testing Enabled (Trouble In) and Testing
Disabled (Trouble Out). When toggling
between Testing Enabled and Testing
Disabled, there is a three minute time
period that separates the two states.
Activating the ASD_Devices command will
post a Trouble into the system which will be
printed out as:
TROUBLE IN 253 08:24:53 AUG 08, 20XX
#8 — SIEMENS BUILDING TECHNOLOGIES —,
ASD TESTING ENABLED, MXL PANEL
Pressing ENTER a second time will cause
the following message to be printed out:
TROUBLE OUT 253 08:25:50 AUG 08, 20XX
#9 — SIEMENS BUILDING TECHNOLOGIES —,
ASD TESTING DISABLED, MXL PANEL
If Test ASD_Devices is activated and left
alone, the system will automatically disable
the test (time out) after four hours.
Test ASD_Devices is inhibited while the
system is initializing or resetting.
Test: Summarize
Use Test Summarize to ignore known
troubles, and instead view one summarized
trouble for an entire module. This is typically
used during installation and commissioning.
Select Summarize and press ENTER. The
System displays the following menu:
Select Mods ON OFF
Test: Summarize - Select_Mods
Use Test Summarize Select_Mods to scroll
through all installed (CSG-M) module
addresses and enable/disable the summa-
rize feature for each module address.
Choose Select_Mods and press ENTER.
The System displays the following: