3-34
Operation
Air Sampling Air Flow Levels at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX
0% Scale >> . . << LOW, Cust Msg 1
010-002 13:23:32 Jan 03,20XX
100% Scale >>! !<< HIGH, Cust Msg
010-010 13:23:31 Jan 03,20XX
42% Scale >>! . << NORM, Cust Msg 10
010-011 13:23:32 Jan 03,20XX
100% Scale >>! . << NORM, Cust Msg 11
List Air Sampling – Trip_pts
Press ENTER when the T in TRIP_PTS is
blinking to select LIST AIR SAMPLING
TRIP_PTS.
The System prompts you to select between
ALARM_TRIP and FLOW_TRIP.
Press ENTER when the A in ALARM_TRIP
is blinking to select LIST TRIP_PTS
ALARM_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE
Type the three-digit NIM-1 (ASP) module
number and three-digit Air Sampling device
address number using the numeric keypad
and press ENTER. The System displays
the current alarm trip point settings for the
address specified:
010-004 P1: 20% P2: 60% ALM: 90%
Print the Air Sampling Alarm Trip Pts
Press PRINT when the A in ALARM_TRIP
is blinking to print the AIR SAMPLING
ALARM_TRIP points.
The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1 (ASP) module
number and press ENTER. The System
sends alarm trip point levels for all devices
on the selected MODULE to the printer.
Air Sampling Alarm Trip Points at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 30%
ALRM: 100%, Cust Msg 1
010-002 13:23:31 Jan 03,20XX, PRE1: 30% PRE2: 50%
ALRM: 90%, Cust Msg 2
010-010 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 50%
ALRM: 100%, Cust Msg 10
010-011 13:23:31 Jan 03,20XX, PRE1: 50% PRE2: 80%
ALRM: 100%, Cust Msg 11
Press ENTER when the F in FLOW_TRIP is
blinking to select LIST TRIP_PTS
FLOW_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE
Type the three-digit NIM-1 (ASP) module
number and three-digit Air Sampling device
address number using the numeric keypad
and press ENTER. The System displays
the current air flow trip point settings for the
address specified:
010-004 LOW: 20% HIGH: 80%
Print the Air Sampling Flow Trip Pts
Press PRINT when the F in FLOW_TRIP
is blinking to print the AIR SAMPLING
FLOW_TRIP points.
The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1 (ASP) module
number and press ENTER.
The System sends air flow trip point levels
for all devices on the selected MODULE to
the printer.
Air Sampling Air Flow Trip Points at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 90%,
Cust Msg 1
010-002 13:23:31 Jan 03,20XX, LOW: 20% HIGH: 80%,
Cust Msg 1
010-010 13:23:31 Jan 03,20XX, LOW: 30% HIGH: 70%,
Cust Msg 1
010-011 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 80%,
Cust Msg 1
List: Percent/ft
Use List Percent/ft to show settings in
percent/ft obscuration of the ILI and ILP
Series detectors.
From the List menu, use the left or right
arrow key to cause the P in PERCENT/FT
to start blinking: