1-18
Description
DI-B3H Ionization Air Duct High
Altitude Detector
The DI-B3H is an ionization detector for use
only in air ducts at altitudes of 3000 to 8000
feet. It must be used with a Series 3 air
duct housing (AD-3I or AD-3RI).
DT-11 Thermal Detector
The DT-11 is a thermal detector for use in
open areas. It uses the DB-11 low profile
surface mounting base or the DB-3S
mounting base with the DB-ADPT adapter.
PE-3 Photoelectric Detector
The PE-3 is a photoelectric detector that
responds to a wide range of both flaming
and smoldering fire conditions. It uses
either the DB-3S low profile surface mount-
ing base or the AD-3ILP or AD-3XRILP air
duct housing.
PE-3T Photoelectric Detector with Heat
Sensor
The PE-3T is a photoelectric detector with
heat sensor that responds to a wide range
of both flaming and smoldering fire condi-
tions. It uses the DB-3S low profile surface
mounting base.
PE-11 Photoelectric Detector
The PE-11 is a photoelectric detector that
responds to a wide range of both flaming
and smoldering fire conditions. It uses the
DB-11 low profile surface mounting base,
the DB-3S mounting base with the
DB-ADPT adapter, or the AD-11P/11PR
air duct housing.
PE-11T Photoelectric Detector with
Heat Sensor
The PE-11T is a photoelectric detector with
heat sensor that responds to a wide range
of both flaming and smoldering fire condi-
tions. It uses the DB-11 low profile surface
mounting base or the DB-3S mounting base
with the DB-ADPT adapter.
PBA-1191 Linear Beam Smoke Detector
The PBA-1191 can detect light or dark
smoke buildup at distances between the
transmitter (X) and receiver (R) of 17 feet to
280 feet. The PBA-1191 can be used in a
variety of areas, including large, narrow, or
high rooms, and rooms with high air
turbulence. The PBA-1191 requires the
PBB-1191 base.
NOTE: Only one PBA-1191, and no
additional devices, can be connected to a
CZM-4 initiating zone.