3-39
Operation
Control: Output on/off
Use Control Output_On/Off to arm or
disarm an output device. In addition, you can
energize or de-energize disarmed output
devices.
From the Control menu, press the Left or
Right arrow key to cause the O in OUTPUT
to start blinking:
CONTROL ARM/DIS OUTPUT ON/OFF
(If you press HELP at this point, the System
displays:
TURN OUTPUTS ON OR OFF
Press HELP again to return to the above
menu.)
Press ENTER while the O in OUTPUT is
blinking to select CONTROL_OUTPUT ON/
OFF.
The System asks for a module number and
device number of the device you wish to turn
on or off (energize or de-energize). Type
the three-digit module number and three-
digit device number using the numeric
keypad and press ENTER. (Enter all
leading zeros.)
The System shows the following display:
253-005 ARM DISARM
The System offers you a choice of arming
or disarming the device.
Use the Right and Left arrow keys to
highlight your choice and press ENTER.
If you have armed the device, you can
press NEXT to display the number of the
next device in the sequence. You can also
press the Up arrow key to return to the
Control menu.
NOTE: You must first disarm a device if
you wish to energize or de-energize it.
When you disarm an output device, the
System automatically annunciates the
disarming as a Trouble and a Partial
System Disable.
If you choose to disarm an output device,
the System then asks if you wish to energize
it or de-energize it:
253-005 ENERGIZE DE ENERGIZE
Use the Right or Left arrow key to energize
or de-energize the device and press ENTER.
Press NEXT to move through the outputs
until you display the ones you want to
change; follow the instructions above for
making the change.
When the System has displayed the
highest numbered device for the module
specified, it returns to the Control menu. To
arm or disarm and energize or de-energize
a device on a different module, follow the
preceding instructions.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)
Control: Loop Arm
Use Control Loop Arm to enable the opera-
tion of a loop of ALD initiating devices.
From the Control menu, press the Left or
Right arrow key to cause the L in
LOOP_ARM to start blinking.
(If you press HELP at this point, the System
displays:
TO ARM ALL INPUTS ON A LOOP
Press HELP again to return to the Control
menu.)
Press ENTER while the L in LOOP_ARM is
blinking to select Control Loop_arm.
The System asks you for the module
number of the ALD loop you wish to arm.
Type the three-digit module number using
the numeric keypad and press ENTER.
(Enter all leading zeros.)
When you arm input devices, the System
automatically annunciates the arming as a
Trouble OUT, and lights the PARTIAL
SYSTEM DISABLE LED.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)