This section provides instructions for
operating the MXL-IQ Control Panel.
Please review the introduction to the
MXL-IQ Control Panel at the beginning of
this manual.
NOTE: See the Table of Contents pages at
the beginning of this manual for the order
of this chapter. Use it to find the answers to
specific questions when you are working
with the System.
Addresses
All modules and devices annunciated on the
MXL-IQ are identified by an address (MMM-
DDD). Each address is in two parts—a
module address (MMM) and a device
address (DDD). The number identifying the
module may be as high as 254, and the
number identifying the device may be as
high as 248. Thus a device on a module
may be identified by any number between
001-001 and 253-250. (See Table 17.)
Fixed Addresses
A module may be assigned to any address
on the System, except for some fixed
addresses that have already been assigned
(See Table 17). The modules communicate
to the MXL-IQ Control Panel through a serial
communications network. The System
continuously supervises all of the modules
for presence and proper operation.
You may assign a module to any address
on the System, and assign addresses in
any order, mixing different types of mod-
ules and leaving gaps in the numbering,
provided you do not use the fixed ad-
dresses.
The specific addresses of the System
modules are described in Table 17.
Chapter
3
Operation
INTRODUCTION
3-1
71ELBAT
sesserddAeludoMdexiF
eludoM
sserddAeludoM
eciveD
sserddA
)egnaR(
0
1
2
3
*
*
*
842
942
052
152
252
352
452
552
esutonoD
)2-BMS(1poolgolanA
)2-BMS(2poolgolanA
BKM
BKM
BKM
1.oN,BKM
devreseR
2-BM
S
M-GSCremmargorP
)devreser(labolG
060-100
060-100
052ot100