1-17
Description
CONVENTIONAL
DEVICES
TRI-B6, TRI-B6R, and TRI-B6D
Intelligent Interface Modules
The TRI-B6 series modules are intelligent
interface modules that interface direct
shorting contact devices with the analog
loops. The TRI-B6 is a single-input module;
the TRI-B6R is a single-input module with
an independently controllable Form C relay;
the TRI-B6D is a dual-input module.
TRI-B6M Addressable Interface Module
The TRI-B6M addressable interface
module interfaces direct shorting contact
devices with the analog loops. The TRI-
-B6M can monitor a normally open or
closed dry contact and it can report the
status of the contact
DI-A3 Ionization High Air-Velocity
Detector
The DI-A3 is an ionization high air velocity
detector for use in open areas, computer
facilities, and air ducts at altitudes of 0 to
4000 feet and at air velocities of 0 to 1200
feet per minute. It uses the DB-3S low
profile surface mounting base.
DI-A3H Ionization High Air-Velocity,
High Altitude Detector
The DI-A3H is an ionization high air
velocity, high altitude detector for use in air
ducts only at altitudes of 3000 to 8000 feet
and at air velocities of 300 to 1200 feet per
minute. It uses the DB-3S low profile
surface mounting base.
DI-B3 Ionization Air Duct Detector
The DI-B3 is an ionization detector for use
only in air ducts at altitudes of 0 to 4000
feet. It must be used with a Series 3 air
duct housing (AD-3I or AD-3RI).
TRI-S, TRI-R, and TRI-D Intelligent
Interface Modules
The TRI-S/R/D series modules are intelligent
interface modules that interface direct
shorting contact devices with the analog
loops. The TRI-S is a single-input module;
the TRI-R is a single-input module with an
independently controllable Form C relay;
the TRI-D is a dual-input module.
CZM-1B6 Remote Conventional Zone
Module
The CZM-1B6 Remote Conventional Zone
Module supports one zone of non-address-
able initiating devices in either Style D
(Class A) or Style B (Class B) configuration,
for a maximum of 15 compatible 2-wire
smoke detectors and an unlimited number
of shorting devices.
The conventional devices described below
are available for use with the MXL-IQ Control
Panel.
The UL identifiers for compatibility are the
same as the model numbers.
DI-3 Ionization Detector
The DI-3 is an ionization detector for use in
open areas at altitudes of 0 to 4000 feet. It
uses the DB-3S low profile surface mount-
ing base.
DI-3H Ionization High Altitude Detector
The DI-3H is an ionization detector for use
in open areas at altitudes of 3000 to 8000
feet. It uses the DB-3S low profile surface
mounting base.