3-40
Operation
Control: Loop Disarm
Use Control Loop Disarm to disable the
operation of a loop of ALD initiating devices.
From the Control menu, press the Left or
Right arrow key to cause the L in
LOOP_DISARM to start blinking.
(If you press HELP at this point, the System
displays:
TO DISARM ALL INPUTS ON A LOOP
Press HELP again to return to the Control
menu.)
Press ENTER while the L in LOOP_DISARM
is blinking to select Control Loop_disarm.
The System asks you for the module
number of the ALD loop you wish to disarm.
Type the three-digit module number using
the numeric keypad and press ENTER.
(Enter all leading zeros.)
When you disarm input devices, the
System automatically annunciates the
disarming as a Trouble IN, and lights the
PARTIAL SYSTEM DISABLE LED.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)
Control: Net Link Request
Use Control Net_Link_Request to connect
or disconnect that particular panel from the
X-Network. When the panel is discon-
nected from the X-Network, the panel
maintains its functions, but it does not
exchange messages with other nodes in the
X-Network.
From the Control menu, press the Left or
Right arrow key to cause the N in
NET_LINK_REQUEST to start blinking.
(If you press HELP at this point, the System
displays:
REQUEST NCC DISCONNECT/RECON NODE
Press HELP again to return to the Control
menu.)
Press ENTER while the N in
NET_LINK_REQUEST is blinking to
disconnect the panel from the X-Network.
To reconnect the panel to the X-Network,
from the Control menu, press the Left or
Right arrow key to cause the N in
NET_LINK_REQUEST to start blinking and
press ENTER.
Control: Air Sampling
Use Control AIR SAMPLING to display and
change the operational characteristics of
the Air Sampling devices.
Press ENTER when the A in AIR SAMPLING
is blinking to select Control AIR SAMPLING.
The System prompts you to select be-
tween ALARM_TRIP and FLOW_TRIP.
Press ENTER when the A in ALARM_TRIP
is blinking to select CONTROL ALARM_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE
Type the three-digit NIM-1 (ASP) module
number and three-digit Air Sampling device
address number using the numeric keypad
and press ENTER. The system displays the
current alarm trip point settings for the
address specified:
010-004 P1: 20% P2: 60% ALM: 90%
Use the numeric keypad and the left and
right arrow keys to modify the value for P1,
P2, and ALM (Alarm). Note that the follow-
ing provisions apply:
P1 must be less than or equal to P2
which must be less than or equal to
ALM. If these values are different, the
System will reject the settings.
P1, P2, and ALM must be even multiples
of 10% or the System will reject the
settings.
Press ENTER when you are finished
modifying the settings. The display should
then show:
TRIP POINTS ACCEPTED