2-18
Installation
Test Response
5. Activate all status devices on the
System.
None of the devices should cause an alarm or trouble condition.
If there is a printer, the System should print the status of report-
ing devices.
As each device is activated, the custom message recorded on
the printer corresponds to the CSG-M printout for that device.
Check that all appropriate responses are activated.
6. CRM-4 relays:
Refer to Control Output On/Off, page
3-38, and toggle each CRM-4 relay
assigned to the System.
Reset the System when this test is
complete.
Verifies proper operation of the connected relay.
8. System Functions:
Check all functions that are defined in
the customer specifications.
Check that the correct relationships between initiating devices
and output functions occur as defined by the customer specifica-
tions.
Check that the appropriate NFPA and local codes are met
(Refer to the CSG-M Logical Function Summary.)
7. CSM-4 relays:
Refer to Control Output On/Off, page
3-38, and toggle each CSM-4 relay
assigned to the System.
Reset the System when this test is
complete.
Verifies proper operation of the connected relay.