Operating the metering panel
110-0134.9 / 14 NXAIR / ≤ 40 kA 107
Replacing protection fuse-links for rated voltage 17.5 kV
Fig. 172: Withdrawable metering part, taken
out of the panel
Removable protection fuse-link
Fixed-mounted voltage transformer
Bolted joint of insulating cover
Remove the upper and lower bolt M8x12 with washer 8.4 mm completely from the three
insulating covers.
Keep the 3 insulating covers, 6 bolts and 6 washers 8.4 mm for later reuse.
Pull the lower end of the protection fuse-link off the clamp by means of a screwdriver.
Pull the upper end of the protection fuse-link off the clamp and remove the protection
fuse-link.
Fig. 173: Insulating cover
removed
Fig. 174: Use of a
screwdriver
Fig. 175: Pulling off the
fuse-link