EasyManua.ls Logo

Siemens NXAIR - Page 193

Siemens NXAIR
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating the contactor panel with panel width 600 mm
110-0134.9 / 14 NXAIR / 40 kA 193
Selection table for HV HRC fuse-links
Rated
voltage
U
r
[kV]
Rated
current
I
r
[A]
Dimensi
on “e“
[mm]
Number of fuse-
links permitted
per phase
Order details
(SIBA)
Order details
(Inter-teknik)
7.2
50
442
1
3010853.50
+S68T.12KV.442.050.08-7.2
63
1
3010853.63
+S68T.12KV.442.063.08-7.2
80
1
3010853.80
+S68T.12KV.442.080.08-7.2
100
1
3010853.100
+S4T.12KV.442.100.08-7.2
125
1
3010953.125
+S4T.12KV.442.125.08-7.2
160
1 or 2
3010953.160
+S4T.12KV.442.160.08-7.2
200
1 or 2
3011054.200
+S4T.12KV.442.200.08-7.2
250
1 or 2
3011054.250
+S4T.12KV.442.250.08-7.2
315
1
3011054.315
+S4T.12KV.442.315.08-7.2
Supplier information : www.siba-fuses.com
Supplier information : www.inter-teknik.com
Replacing HV HRC fuse-links
NOTICE
Undetected damage
Tripped HV HRC fuse-links can cause hidden damages on the other
HV HRC fuse-links.
Always replace all HV HRC fuse-links, even if only one HV HRC fuse-link
has tripped.
INFORMATION
Electrical indication of tripped fuse-links
Electrical indications at the panel or in the remote control room are automatically
reset to operating mode by resetting the mechanical indicator for the
HV HRC fuse-links.
INFORMATION
Recommended order of action
The HV HRC fuse-links in the middle phase L2 are only accessible after removing
the HV HRC fuse-links from the neighboring phase L3.
First, remove the HV HRC fuse-links from the outer phases L1 and L3 on
the left and right side of the contactor truck. Next, remove the HV HRC
fuse-links from the middle phase L2.

Table of Contents

Other manuals for Siemens NXAIR

Related product manuals