Operating the contactor panel with panel width 600 mm
192 NXAIR / 40 kA 110-0134.9 / 14
When inserting a new HV HRC fuse-link, the striker pin must always point to the lower clamp. The position of
the striker pin is marked on the HV HRC fuse-link by a triangle representing an arrow (8).
Fig. 345: Seen from right side of truck: Striker pin pointing to lower clamp
Permissible HV HRC fuse-links
The specified SIBA HV HRC fuse-links are motor protection back-up fuse-links according to IEC 60282-1.
The dimensions of the HV HRC fuse-links correspond to DIN 43625.
NOTICE
Maloperation
Contactor trucks are exclusively designed for operation with specific
HV HRC fuse-links. Using the different type of fuse-links may cause damages on
the panel.
Use only the fuse-link types listed in the following table.
Do not mount bridging links instead of HV HRC fuse-links.
8