Operating the switch-disconnector panel
236 NXAIR / 40 kA 110-0134.9 / 14
Replacing HV HRC fuse-links
NOTICE
Undetected damage
Tripped HV HRC fuse-links can cause hidden damages on the other HV HRC
fuse-links.
Always replace all HV HRC fuse-links, even if only one HV HRC fuse-link
has tripped.
INFORMATION
Final procedure steps
After closing the high-voltage door, the panel can be integrated into the
course of operation again.
Preconditions
Set of proper HV HRC fuse-links available
Switch-fuse combination in OPEN position
Feeder earthing switch in CLOSED position
High-voltage door open
Procedure
Fig. 418: Front view: Arrangement of HV HRC fuse-links
(high-voltage door open )
(1)
HV HRC Fuses
Select one of the phases. Remove the HV HRC fuse-link by pulling it out of the clamps.
1