Loading...
Accessing the connection compartment through the front
340 NXAIR / 40 kA 110-0134.9 / 14
NOTICE
Damages inside the switching-device compartment
Damages inside the switching-device compartment / voltage transformer
compartment due to incorrect or incomplete installation of the partition / bushing
plate.
To fasten the partition / bushing plate, always assemble all bolted joints all
around, and screw them in up to the end of the thread.
Preconditions
Feeder earthing switch in CLOSED position
High-voltage door open
Door to voltage transformer compartment open
In the switching-device compartment and in the voltage transformer compartment:
Low-voltage connectors stowed away
Bushing plate and associated connecting elements available:
8 bolts M8x20 with contact washers and plain washers size 8 acc. to ISO 7093
3 bolts M8x20 with contact washers
Connection leads and associated connecting elements available:
3 nuts M8 with contact washers and plain washers
Vertical partition and associated connecting elements available:
8 bolts M8x20 with contact washers and plain washers size 8 acc. to ISO 7093
Protection plate and associated connecting elements available:
4 nuts M8 with contact washers
Voltage transformer compartment and associated connecting elements available:
14 bolts M8x20 with contact washers
Lid of metal cover and associated connecting elements available:
2 bolts M8x20 with contact washers
Wiring duct cover and associated connecting elements available:
3 bolts M8x20 with contact washers
Labyrinth and associated connecting elements available:
4 bolts M8x16 with contact washers
2 nuts M8 with contact washers
Procedure
Install the bushing plate with bushings.
Fix the bushing plate by screwing the bolts hand-tight:
8 bolts M8x20 with contact washers and plain washers size 8
acc. to ISO 7093 (1)
3 bolts M8x20 with contact washers (2)
Tighten the bolts with a tightening torque of 25 Nm.