Accessing the connection compartment through the front
110-0134.9 / 14 NXAIR / 40 kA 341
Fig. 629: 11 bolted joints on bushing plate
Fix the connecting leads (4). To do this, mount the connecting elements (3) and tighten
hand-tight:
3 nuts M8 with contact washers and plain washers
Tighten the nuts with a tightening torque of 25 Nm.
Fig. 630: 3 bolted joints at the cable connections (central joint covered)
Install the vertical partition in the connection compartment.
1
2