802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11 237/293
Operation
Disconnector panel as of 2000 A: De-earthing the feeder
1
Initial situation
2
Push the interrogation lever downwards and
hold it.
3
Push the control gate to the right.
4
Switch the three-position disconnector from
EARTHED to OPEN position (insert the
operating lever and turn 90° counter-
clockwise).
5
Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).