802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11 37/293
Description
Cellpack 50400 EPDM 2x CTS 630A 24kV 1x CKS 630A 24kV - - IEC
25…300 2x CTS 630A 24kV* 1x CKS 630A 24kV* - - IEC
50…240 EPDM 1x CTS 630A 24kV 1x CTKS 630A 24kV CTKSA - IEC
25…240 1x CTS 630A 24kV* 1x CTKS 630A 24kV* CTKSA - IEC
Ample 25…400 EPDM 1x AQT3-15/630 1x AHT3-15/630 AHY5WZ7 - GB/DL
35…500 1x AQT3-24/630* 1x AHT3-24/630* AHY5WZ7 - GB/DL
3 cables per panel and phase
Nexans
Euromold
35…300 EPDM 1x 430TB/G 2x 300PB/G - - IEC, GOST, GB/DL
1x K430TB/G* 2x K300PB/G* - - IEC
1x K430TB/G-CSxxx* 2x K300PB/G-CSxxx* - - GOST, GB/DL
35…300 EPDM 1x 480TB/G 2x 800PB/G - - IEC
1x K480TB/G* 2x K800PB/G* - - IEC
50…630 EPDM 1x 484TB/G 2x 804PB/G - - IEC
35…630 1x K484TB/G* 2x K804PB/G* - - IEC
800…1200 EPDM 1x 489TB/G 2x 809PB/G - - IEC
1x K489TB/G* 2x K809PB/G* - - IEC
nkt cables 25…300 Silicon
e
1x CB 12-630 2x CC 12-630 - - IEC
25…500 1x CB 17,5-630 2x CC 17,5-630 - - GOST, GB/DL
25…300 1x CB 24-630* 2x CC 24-630* - - IEC, GOST, GB/DL
185…500 Silicon
e
1x CB 24-1250-2 2x CC 24-1250-2 - - IEC
95…500 1x CB 24-1250-2* 2x CC 24-1250-2* - - IEC
400…630 Silicon
e
1x CB 36-630(1250) 2x CC 36-630(1250) - - IEC, GOST, GB/DL
1x CB 36-630(1250)* 2x CC 36-630(1250)* - - IEC, GOST, GB/DL
630…1000 Silicon
e
1x CB 42-1250-3 2x CC 42-2500-3 - - IEC
1x CB 42-1250-3* 2x CC 42-2500-3* - - IEC
Tyco
Electronics
Raychem
25…300 Silicon
e
1x RSTI-58xx 2x RSTI-CC-58xx - - IEC
1x RSTI-58xx* 2x RSTI-CC-58xx* - - IEC
25…300 Silicon
e
1x RSTI-58xx-CEE01 2x RSTI-CC-58xx-CEE01 - - GOST
1x RSTI-58xx-CEE01* 2x RSTI-CC-58xx-CEE01* - - GOST
400…800 Silicon
e
1x RSTI-395x 2x RSTI-CC-395x - - IEC
1x RSTI-595x* 2x RSTI-CC-595x* - - IEC
400…800 Silicon
e
1x RSTI-595x-CEE01 2x RSTI-CC-595x-CEE01 - - GOST
1x RSTI-595x-CEE01* 2x RSTI-CC-595x-CEE01* - - GOST
Cellpack 50240 EPDM 1x CTS 630A 24kV 2x CTKS 630A 24kV - - IEC
25…240 1x CTS 630A 24kV* 2x CTKS 630A 24kV* - - IEC
1
At a continuous current of more than 1150 A, cable sealing ends with tin-plated, nickel-plated or silver-plated cable lugs are required.
2
Observe the actual current- and short-circuit-carrying capacity of the cables and sealing ends.
Circuit-breaker panel 630 A, 1000 A Switch-disconnector panel 630 A Disconnector panel 1000 A Ring-main panel 630 A Vacuum
contactor panel Circuit-breaker panel with top-rear cable connection 1250 A
1
Panel spacing 600 mm
Make Conductor
cross-
section
2
Insulation
Cable T-plugs Coupling inserts/
coupling plugs
Surge arresters with coupling inserts According to
standard
[mm
2
] bolted bolted with arresters Coupling inserts
GOST
(Russia, CIS)
GB/DL (China)
12 kV
24 kV*
12 kV
24 kV*
additionally

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXPLUS C and is the answer not in the manual?

Siemens NXPLUS C Specifications

General IconGeneral
BrandSiemens
ModelNXPLUS C
CategoryCircuit breakers
LanguageEnglish

Related product manuals