Engineer Management
90
Siemens Building Technologies
Fire Safety & Security Products 07.2009
>
= Input changes from idle to triggered state
> = Input changes from triggered to idle state
Resistance value For the physical inputs (except main board SM110) the actual resistance value of the input is shown. If radio
messages are programmed on the inputs, the quality of the radio transmission is indicated as a %.
19.8.3 Soak Test
[TM83] Input soak test This menu function enables the individual inputs in individual partitions to be switched to soak test. This
provides the input with all functions except that instead of triggering an alarm it is only written to the log. This
means that a triggering of an internal burglar alarm line in the soak test is only written to the log if the system
is full set. The advantage of this compared with switching off the input is that a report of this input is available
in the log.
Partitions Only the inputs which are assigned to the chosen partition can be switched to soak test.
Interrogate inputs By pressing the ? key, the inputs which are in soak test can be interrogated in turn. In doing so the ? key is
pressed on the indication with the choice of inputs. The system then shows the next input which is switched
to soak test. By pressing the ? key again, the other inputs in the soak test can be interrogated in the same
way.
19.8.4 Output Test
[TM84] Test outputs This menu function enables all outputs to be switched ON and OFF in the individual partitions.
Reset When leaving the individual output test, the outputs are automatically reset to their original state. The bell
outputs are activated for only a maximum of 5 seconds. The strobe light outputs are activated for a maximum
of 5 minutes.
19.8.5 Transmission Test
[TM85] Transmission test This menu function enables a transmission test to be carried out. In doing so, the transmission test trans-
mission line is triggered. After the transmission test to Receiver 1 or Receiver 2 has been performed, the
system remains in the transmission test. This enables communication with Sylcom to be checked.
Receivers The transmission test is carried out to Receiver 1 and/or Receiver 2, depending on whether the transmis-
sion test transmission line ("Line Telecom Options" (TM66) in the engineer menu) is programmed to trans-
mission or not.
Customer number The customer number programmed for partition 1 is transmitted.
Transmission information During transmission test, the actual transmission state is continuously displayed on the display.
Transmission test Central control unit is on transmission test.
Line disturbed The telephone line is disturbed.
Line occupied The line is occupied.
Dial number The central control unit dials the programmed telephone number.
Change destination The central control unit changes to the other receiving centre.
Time between dialling The central control unit waits for the next dialing.
Waiting for request to
send
Waiting for request to send: The central control unit is waiting for the request to send from the receiving
centre.
No dialling tone The central control unit does not detect a dialing tone.
Request to send received The central control unit has received the request to send from the receiving centre.
No request to send The central control unit has not received a request to send from the receiving centre within the specified
time.
Data transmission Data transmission is taking place.
Wait for confirmation The central control unit is waiting for confirmation of the transmission to the receiving centre.
Confirmation received The central control unit has received confirmation of transmission from the receiving centre.
No confirmation The central control unit has received no confirmation of transmission within the specified time.
New message The central control unit provides a new message.
Transmission repeating The central control unit repeats the transmission.
Transmission OK The transmission was successful.
Wait for dialling tone The central control unit is waiting for the dialing tone.
Transmission fault A transmission fault has occurred.
New attempt The central control unit is starting a further transmission attempt.
Pause The central control unit is waiting, character "C" on the telephone number.
Tel.1 Rec.1 Telephone number 1 of Receiver 1
Tel.2 Rec.1 Telephone number 2 of Receiver 1
Tel.3 Rec.1 Telephone number 3 of Receiver 1