8.2.19 Panic Alarm
Panic Alarm This output is activated immediately a panic alarm input (remote keypad or panic alarm input) is triggered.
This output will reset when a user confirms the alarm.
NOTE
If the system parameter “Engineer Reset On” for the particular alarm, only the engineer PIN can
reset the output.
.
UK, HU, BE Is reset when the alarm memory is deleted.
All other
country versions
Is automatically reset after 10 seconds.
8.2.20 Burglar Alarm
Burglar Alarm This output is activated if a burglar alarm is triggered for the assigned partition or system.
This output will reset when a user confirms the alarm.
NOTE
If the system parameter “Engineer Reset On” for the particular alarm, only the engineer PIN can
reset the output.
8.2.21 Tamper Alarm
Tamper Alarm This output is activated if a tamper alarm is triggered for the assigned partition or system.
This output will reset when a user confirms the alarm.
NOTE
If the system parameter “Engineer Reset On” for the particular alarm, only the engineer PIN can
reset the output.
8.2.22 Abort Alarm
Abort Alarm
NOTE
There is a restriction using “Abort Alarm” or “Confirmed Alarm” for the same partition. It is only
possible to choose one of those.
This output is following the assigned partition parameter “Transmission Verify Method” in the menu System
Input Transmission “Abort/Confirmed P(X)”
This output is activated if the “Alarm Abort” was successfully transmitted.
8.2.23 Confirmed Alarm
Confirmed Alarm
NOTE
There is a restriction using “Abort Alarm” or “Confirmed Alarm” for the same partition. It is only
possible to choose one of those.
This output is following the assigned partition parameter “Transmission Verify Method” in the menu System
Input Transmission “Abort/Confirmed P(X)”
This output is activated if the “Alarm Confirmation” was successfully transmitted.