Partitions
57
Siemens Building Technologies
Fire Safety & Security Products 07.2009
9.12 Forced Set
Forced Set This parameter defines whether or not the partition permits forced setting. Forced setting means that trig-
gered input lines are automatically bypassed when assigned partition is set.
However, all of the following conditions must be fulfilled:
z Triggered input lines must be defined as capable of being bypassed.
z Not more than the defined number of inputs (50% or ONE defined by parameter "bypass mode") may be
bypassed.
z When setting with a PIN the user must have forced setting authority (setting via an input is equivalent to
forced setting)
The following four options are available for this parameter.
0 = No Authority
Forced setting is not possible.
1 = Until Unset
Forced setting is possible whereby the bypassed lines remain bypassed until assigned partition is
unset.
2 = Until Input quiescent state
Forced setting is possible whereby the bypassed lines remain bypassed until assigned partition is
unset or the bypassed line is in quiescent state.
3 = Forced Set
Forced setting possible whereby the bypassed lines immediately trigger an alarm when forced setting
takes place.
9.13 Transmission
9.13.1 Burglar Alarm/P. Set
Part Set Transmission of
Burglar Alarm
This parameter defines whether or not transmission is enabled on part set or unset in the event of a burglar
alarm.
B = Enabled
- = Disabled
9.13.2 Tamper Alarm/P. Set
Part Set Transmission of
Tamper Alarm
This parameter defines whether or not transmission is enabled on part set or unset in the event of a tamper
alarm.
T = Enabled
- = Disabled