Loading...
Service
79
Siemens Building Technologies
Fire Safety & Security Products 07.2009
14.2.2 Protocol (Service 2)
Protocol for Service 2 Either Sylcom or one of the integrated pager protocols can be selected here.
Pager protocol With the pagers, the Service 2 site number (8-digit) followed by an alarm code (1-digit) is transmitted.
Pager alarm code The alarm codes mean the following alarm types:
z Code 1 Æ Panic alarm
z Code 2 Æ Burglar alarm
z Code 3 Æ Panic alarm
z Code 4 Æ Voltage alarm
z Code 5 Æ Voltage alarm
z Code 8 Æ Other alarms
Log book to Sylcom
Pager TAMTAM
Pager TATOO
Pager
Pager KOBBY
Siren
*GSM SMS SMS Header: Home panel
14.2.3 GSM
GSM SMS protocol If this protocol is selected, the user is able to set 16 characters for the GSM header.
IP/GSM(GPRS) Module SMN 43 – sending SMS
z In combination with the IP/GSM(GPRS) module (SMN 43) Sintony can send a
SMS message, independent from the alarm transmission. Therefore the func-
tionality “Transmit message to Service 2” is used.
z If this option is chosen in the control panels in combination with a “Serial port“
set to SMN42 (ARC1 parameter), then the according message is generated from
Sintony and the SMN43 sends a SMS to the phone number.
z In the “Inputs transmission” and “System Input Transmission” definition the engi-
neer has to choose the message to send.

Table of Contents