6.3.35 Panic Pushbuttons of Remote Keypads
Panic Pushbuttons
of Remote Keypads
NOTE
These inputs are triggered from the panic pushbuttons on the remote keypads (refer to keypad in-
structions).
Only "unused", "Silent panic" or "Audible panic" can be programmed as the input type.
The input can be assigned to the partitions 1 to 6.(1 to 2 for SI120)
For triggering, refer to "Audible panic alarm" or "Silent panic" input types.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are
preset:
X X Cannot full set
X Cannot part set
X X Block lock not released
X X X Buzzer
X X X Fault
X X X Transmission line fault
Partition parameters:
X = Triggering regardless of the partition mode.
6 = Triggering only if "Forced Set" parameter ->”Not Allowed” is chosen.
6.3.36 System Tamper
System Tamper
NOTE
This input is permanently defined as a "tamper" input type. System tamper is triggered by:
- tamper contact from the central control unit and E-bus components
- or by missing E-bus components
The input triggers a tamper alarm from all partitions.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are
preset:
X X Cannot full set
X Cannot part set
X X Block lock not released
X X X Buzzer
X X X Fault
X X X Transmission line fault
Partition parameters:
X = Triggering regardless of the partition mode.