Inputs
37
Siemens Building Technologies
Fire Safety & Security Products 07.2009
6.3.37 Mains Failure
Mains Failure
NOTE
This event type is a synthetic input (internally created by the system) and not triggered by a physi-
cal input. Function description see in section “Synthetic Inputs”. Only parameter settings are de-
scribed here.
A delay time (000 to 127 minutes/seconds) can be programmed for the “Mains Failure” power
supply fault synthetic input type. In this case a fault is only triggered if it persists longer than this
delay time.
The input triggers a mains failure in the system from all partitions.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are
preset:
X X Cannot full set
X Cannot part set
X X Block lock not released
X X X Buzzer
X X X Fault
X X X Transmission line fault
Partition parameters:
X = Triggering regardless of the partition mode.
6 = Triggering only if "Forced Set" parameter ->”Not Allowed” is chosen.
6.3.38 Battery Failure
Battery Failure
NOTE
This event type is a synthetic input (internally created by the system) and not triggered by a physi-
cal input. Function description see in section “Synthetic Inputs”. Only parameter settings are de-
scribed here..
A delay time (000 to 127 minutes/seconds) can be programmed for the “Battery Failure” synthetic
input type. In this case a fault is not triggered until it has persisted longer than this time. Using
SMX29, the delay time has to be longer than 60 seconds.
The input triggers a Battery fault in the system from all partitions.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are
preset:
X X Cannot full set
X Cannot part set
X X Block lock not released
X X X Buzzer
X X X Fault
X X X Transmission line fault
Partition parameters:
X = Triggering regardless of the partition mode.
6 = Triggering only if "Forced Set" parameter ->”Not Allowed” is chosen.