Outputs
50
Siemens Building Technologies
Fire Safety & Security Products 07.2009
8.2.34 Emergency 1-5 (1-2 for SI120)
Emergency Exit 1 This output is activated by the input “Emergency Exit 1”. The activation duration is set in the partition pa-
rameters “Emergency Exit”.
NOTE
The emergency output function is, not active in the unset state.
Emergency Exit 2 Same function as emergency output 1, but activated by ”Emergency Exit 2” input.
Emergency Exit 3 Same function as emergency output 1, but activated by ”Emergency Exit 3” input.
Emergency Exit 4 Same function as emergency output 1, but activated by ”Emergency Exit 4” input.
Emergency Exit 5 Same function as emergency output 1, but activated by ”Emergency Exit 5” input.
8.2.35 Universal 1 / Universal 2
Universal 1 This output is activated for corresponding activation time (127 seconds/minutes). If the activation time is 000,
the output remains active until a valid PIN is entered at the keypad, then the input will change to normal
state. The output is activated regardless of the state of the assigned partition (full set / part set / unset).
NOTE
This output will not create an event log.
Precondition: Input Universal Input 1 has been triggered and the delay time is lapsed.
Universal 2 Acts on “Universal Inputs 2”. Function is identical to “Universal 1”.
8.2.36 Calendar output 1 – 2 (SI220 only)
Calendar Output 1 - 2 These outputs can be triggered via Calendar.
8.2.37 Remote Control 1 – 2
Remote Control 1 This output can be triggered via a telephone line with DTMF commands. It is activated for 2 seconds.
Remote Control 2 This output can be triggered via a telephone line with DTMF commands. It is activated for 2 seconds.
8.2.38 Video Recorder
Video Recorder This output is activated for the programmed activation time (127 minutes) on a video alarm.
Alarm For Recorder
France
This output is activated if a burglar alarm is triggered in the assigned partition. It is reset when the partition is
switched to unset or if a valid PIN for this partition has been entered on an authorized remote keypad.
8.2.39 Burglar for Transmission
Burglar for transmission This output is activated if a Burglar has to be transmitted.
8.2.40 Seismic Activation
Vibration
(Vault Sensor Test)
This output is used to test periodically seismic detector.
If a “Vault Sensor” input is programmed, this output is set for 5 seconds in a random time of between 30 and
90 minutes. With this output, the test generator for structure-borne sound can now be triggered in order to
test the vault sensor alarm inputs.
Æ This means that this output type operates only in conjunction with a “Vault Sensor” input.