Inputs
29
Siemens Building Technologies
Fire Safety & Security Products 07.2009
6.3.24 BA Full Set only
Burglar Alarm Full Set only Brief description: BA external; internal inactive
On part set: No triggering in the assigned partition.
On full set: Direct triggering in the assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
X External bell
X Strobe light
X X Cannot full set
X Alarm in memory
X X Block lock not released
5 Buzzer
X Burglar alarm system transmission line
X Burglar alarm partition transmission line
X Transmission line input
Partition parameters:
X = Triggering regardless of the partition mode.
5 = Triggering only if “Buzzer On” in the keypad parameter is chosen.
6.3.25 BA Full or Part Set
Burglar Alarm Full/Part Set Brief description: BA external; internal
Direct triggering on Part and Full set in the assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
1 X External bell
X 2 Internal bell
1 X Strobe light
X X Cannot full set
X Cannot part set
X X Alarm in memory
X X Block lock not released
5 5 Buzzer
3 X Burglar alarm system transmission line
3 X Burglar alarm partition transmission line
3 X Transmission line input
Partition parameters:
X = Triggering regardless of the partition mode.
1 = Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 = Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
3 = Triggering only if "transmission" parameter is chosen.
5 = Triggering only if “Buzzer On” in the keypad parameter is chosen.