Default 4
For example, if Modbus value is:
4 = 40 ms
1050 = 10500 ms
Transformer Type
(Address 15) This register defines the transformer type.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 2 (Dy-11)
Default 2
Neutral-Point Treatment (Group 1)
(Address 16) This register defines the neutral-point treatment method.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 2
0 = Solid
1 = Isolated
2 = Compensated
Default 2 = Resonant
Language
(Address 17) This register defines the device language.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 4
0 = English
1 = Deutsch
2 = Español
3 = Portugués
4 = Français
Default 1 = Deutsch
Voltage-Transformer Secondary/Low-Power Voltage Transformer
(Address 18) This register contains the selected low-power voltage transformer/voltage-transformer secondary
voltages.
Modbus Registers
B.4 Register-Type Data – Holding Registers
114 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019