Address Min/Max Value Parameters Default Unit Type
33 0, 30 to 240 T3 0 s uInt16
34 0, 50 to 2000 I
max
alarm setting 0 A uInt16
35 0, 50 to 2000 I
max
warning setting 0 A uInt16
36 0 to 120 I
max
alarm time setting 0 min uInt16
37 0 to 120 I
max
warning time setting 0 min uInt16
38 0 to 900 Primary-voltage correction 0 V uInt16
39 0 to 359 Transformer angle 330 degrees uInt16
40 0, 2 to 300 I
dir
(Group 1) 10 1/10 A uInt16
41 10 to 360 Sensor voltage 200 1/10 kV uInt16
42 0 to 1 Active group 0 – uInt16
43 0, 4 to 20000 Ground-fault trip value (I
N
>) (Group 2) 600 1/10 A uInt16
44 4 to 6000 Ground-fault response time (tI
N
>) (Group 2) 100 x10 ms uInt16
45 0 to 100 Neutral-point displacement voltage V
NG
>
(Group 2)
0 % uInt16
46 4 to 6000 Neutral-point displacement time tV
NG
>
(Group 2)
4 x10 ms uInt16
47 0, 2 to 300 I
dir
(Group 2) 10 1/10 A uInt16
48 0 Capacitor voltage 0 – uInt16
49 1000 to 36000 Auto calibration voltage 20 000 V uInt16
50 0 to 1 Ground-current acquisition 0 – uInt16
51 0 to 1 DO configuration 0 – uInt16
52 – Reserved for future use – – –
53 – Reserved for future use – – –
54 0 to 60000 Crossblocktimer 100 ms uInt16
55 25 to 150 Ground sensor 60 A uInt16
56 0 to 1 I
1
power-flow direction 0 – uInt16
57 0 to 1 I
2
/I
N
power-flow direction 1 – uInt16
58 0 to 1 I
3
power-flow direction 0 – uInt16
59 0 to 1 P, Q sign 0 – uInt16
60 0 to 2 Neutral-point treatment (Group 2) 1 – uInt16
61 – Reserved for future use – – -
62 – Reserved for future use – – -
63 – Reserved for future use – – -
64 – Reserved for future use – – -
65 – Reserved for future use – – -
66 – Reserved for future use – – -
67 – Reserved for future use – – -
68 – Reserved for future use – – -
69 – Reserved for future use – – -
70 0 to 100 Under-voltage phase threshold for ground
fault V<
0 % uInt16
71 0, 100 to 170 Over-voltage phase threshold for ground
fault V>
0 % uInt16
72 0, 1 to 300 3I0 Delta pulse off-on 0 % uInt16
73 0, 20 to 2000 Pulse-on duration 0 x10 ms uInt16
74 0, 20 to 2000 Pulse-off duration 0 x10 ms uInt16
Modbus Registers
B.2 Implementation of the Modbus Protocol
98 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019