OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
200 Function Manual, 12/2017, A5E03735815-AF
Status "Bad" (8000_0000 - FFFF_FFFF)
Error code
(hex)
Name
Meaning
80710000
BadHistoryOperationInvalid
The history details parameter is not valid.
80720000 BadHistoryOperation
Unsupported
The server does not support the requested operation.
80730000 BadWriteNotSupported The server not does support writing the combination of value, status and
timestamps provided.
80740000 BadTypeMismatch The value supplied for the attribute is not of the same type as the attribute's
value.
80750000
BadMethodInvalid
The method id does not refer to a method for the specified object.
80760000
BadArgumentsMissing
The client did not specify all of the input arguments for the method.
80770000
BadTooManySubscriptions
The server has reached its maximum number of subscriptions.
80780000 BadTooManyPublish
Requests
The server has reached the maximum number of queued publish requests.
80790000
BadNoSubscription
There is no subscription available for this session.
807A0000 BadSequenceNumber
Unknown
The sequence number is unknown to the server.
807B0000
BadMessageNotAvailable
The requested notification message is no longer available.
807C0000 BadInsufficientClientProfile The Client of the current Session does not support one or more Profiles that
are necessary for the Subscription.
80BF0000
BadStateNotActive
The sub-state machine is not currently active.
807D0000
BadTcpServerTooBusy
The server cannot process the request because it is too busy.
807E0000
BadTcpMessageTypeInvalid
The type of the message specified in the header invalid.
807F0000 BadTcpSecureChannel
Unknown
The SecureChannelId and/or TokenId are not currently in use.
80800000
BadTcpMessageTooLarge
The size of the message specified in the header is too large.
80810000 BadTcpNotEnough
Resources
There are not enough resources to process the request.
80820000
BadTcpInternalError
An internal error occurred.
80830000
BadTcpEndpointUrlInvalid
The Server does not recognize the QueryString specified.
80840000
BadRequestInterrupted
The request could not be sent because of a network interruption.
80850000
BadRequestTimeout
Timeout occurred while processing the request.
80860000
BadSecureChannelClosed
The secure channel has been closed.
80870000 BadSecureChannelToken
Unknown
The token has expired or is not recognized.
80880000
BadSequenceNumberInvalid
The sequence number is not valid.
80890000 BadConfigurationError There is a problem with the configuration that affects the usefulness of the
value.
808A0000 BadNotConnected The variable should receive its value from another variable, but has never
been configured to do so.
808B0000 BadDeviceFailure There has been a failure in the device/data source that generates the value
that has affected the value.
808C0000 BadSensorFailure
There has been a failure in the sensor from which the value is derived by the
device/data source.
808D0000
BadOutOfService
The source of the data is not operational.