3-7
ET 200L Distributed I/O Device
EWA-4NEB 780600902-05
In the case of new variants of the following components, the load voltage terminals 1L+,
2L+, and 3L+ used for the sensor power supply of the inputs can be protected using a
circuit breaker with a maximum of 6 A (B or C characteristic).
Kapitel
Komponente MLFB neue Variante MLFB alte Variante
8.1 ET 200L with 16 DI 6ES7131-1BH01-0XB0 6ES7131-1BH00-0XB0
8.3 ET 200L with 32 DI 6ES7131-1BL01-0XB0 6ES7131-1BL00-0XB0
8.5 ET 200L with 16 DI/DO in
each case
6ES7133-1BL01-0XB0 6ES7133-1BL00-0XB0
!
Warning
In the old variants of the above components, the sensor power supply may only be
loaded with 5 A per input byte. The load voltage terminals 1L+, 2L+, and 3L+ should
be protected accordingly.
Protected by cir-
cuit breaker
Wiring