EasyManua.ls Logo

Siemens SIMATIC ET 200L - Page 71

Siemens SIMATIC ET 200L
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-7
ET 200L Distributed I/O Device
EWA-4NEB 780600902-05
Voltages, Currents, Potentials
Rated supply voltage for
electronics (4L+, 5L+)
24 V DC
S Reverse polarity
protection
Yes
S Power failure with-
stand time
At least 20 ms
Rated load voltage
(1L+, 2L+ and 3L+)
24 V DC
Aggregate current of outputs (per byte)
S Horizontal installation
Up to 30 _C Max. 4 A
Up to 40 _C Max. 3 A
Up to 60 _C Max. 2 A
S All other installation
positions
Up to 40 _C Max. 2 A
Galvanic isolation
S Between channels No
S Between channels and
PROFIBUS-DP
Yes
Insulation tested with 500 V DC
Power input
S from supply voltage
L4+/L5+
Max. 70 mA
S from load voltage L1+
and L2+/L3+ (without
load)
Max. 50 mA per load
group
Power loss of module Typically 5 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic function Yes
S Bus monitoring PRO-
FIBUS-DP
Red ”BF” LED
S Monitoring of elec-
tronics power supply
Green ”ON” LED
Actuator Selection Data
Output voltage
S At signal ”1” At least L1+ (– 3 V) or
L2+/L3+ (3 V)
Output current
S At signal ”1”
Rated value
Permissible range
0.5 A
1 mA to 0.5 A
S At signal ”0”
(residual current)
Max. 1 mA
Output delay (with resistive load)
S With ”0” after ”1” Max. 50 µs
S With ”1” after ”0” Max. 200 µs
Load resistance range 41 W to 28 kW
Lamp load Max. 5 W
Parallel connection of two outputs
S For redundant control
of load
Possible (outputs in same
group only)
S For performance im-
provement
Not possible
Driving a digital input Possible
Switching frequency
S Resistive load Max. 100 Hz
S Inductive load to
IEC 947-5-1, DC13
Max. 0.5 Hz
S Lamp load Max. 8 Hz
Limitation of voltage in-
duced on circuit interrup-
tion
Typically L1+ (– 55 V) or
L2+/L3+ (– 55 V)
Short-circuit protection
S Response threshold
Yes
Typically 0.7 A to 1.5 A