8-10
ET 200L Distributed I/O Device
EWA-4NEB 780600902-05
The following table shows the technical data of the L 32 DI DC 24 V elec-
tronics block.
Dimensions and Weight
Dimensions
W
HD (mm)
1456060.5
Weight Approx. 150 g
Module-Specific Data
Baud rate 9.6; 19.2; 45,45*; 93.75;
187.5; 500 and
1500 kBaud
Bus protocol PROFIBUS-DP
FREEZE compatibility Yes
Number of inputs 32
Cable length
S Unshielded Max. 600 m
S Shielded Max. 1000 m
Manufacturer ID 0015
H
Voltages, Currents, Potentials
Rated supply voltage for
electronics (4L+, 5L+)
24 V DC
S Reverse polarity
protection
Yes
S Power failure with-
stand time
At least 20 ms
Rated load voltage
(1L+, 2L+ and 3L+)
24 V DC
Maximum number of in-
puts driven simultaneously
32
Galvanic isolation
S Between channels No
S Between channels and
PROFIBUS-DP
Yes
Insulation tested with 500 V DC
Power input
S from supply voltage
L4+/L5+
Max. 70 mA
S from load voltage L1+
and L2+/L3+ (without
load)
Max. 100 mA per load
group
Power loss of module Typically 3.2 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic function Yes
S Bus monitoring PRO-
FIBUS-DP
Red ”BF” LED
S Monitoring of elec-
tronics power supply
Green ”ON” LED
Sensor Selection Data
Input voltage
S Rated value 24 V DC
S At signal ”1” 13 to 30 V
S At signal ”0” -30 to 5 V
Input current
S At signal ”1” Typically 5 mA at 24 V
Input delay
S With ”0” after ”1” 2.0 to 4.5 ms
S With ”1” after ”0” 2.0 to 4.5 ms
Input characteristic To IEC 1131-2 Type 1
Connection of 2-wire
BEROs
Possible
S Permissible closed-cir-
cuit current
Max. 1.5 mA
* If you want to run the ET 200L, ET 200L–SC or ET 200L–SC IM–SC at a transmission rate of 45.45 kbps, you
must use an updated device master file or STEP 7 as of 4.02 (K4.02.6).
Technical Data
T 200L Electronics Blocks – Technical Da