EasyManua.ls Logo

Siemens SIMATIC ET 200PA SMART - 10.4.1.2 Parameters of the AI 8 x 13 bits

Siemens SIMATIC ET 200PA SMART
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
Table 10-10 Overview of the parameters of SM 331; AI 8 x 13 Bit
Parameters Range of values Default Parameter
type
Scope
Measurement
Measurement type
disabled
Voltage V
Current I
Resistance R, PTC
Thermal resistance RTD,
silicon temperature sensors
V
dynamic
Channel
Measuring range
Voltage
± 50 mV; ± 500 mV; ±1 V;
1 V to 5 V
± 5 V; 0 V to 10 V; ± 10 V
± 10 V
Current
0 mA to 20 mA; 4 mA to 20 mA; ± 20 mA
± 20 mA
Resistance
0 Ω to 600 Ω; 0 kΩ to 6 kΩ; PTC
600 Ω
Thermoelectric resistance (linear)
Pt 100 Klima / Standard
Ni 100 Klima / Standard
Ni 1000 Klima / Standard
LG-Ni 1000 Klima / Standard
KTY83/110
KTY84/130
Pt 100
Standard
Temperature coefficient
Pt 100
0.003850 Ω/Ω/ °C (IST-90)
Ni 100 / Ni 1000
0.006180 Ω/Ω/ °C
LG-Ni 1000
0.005000 Ω/Ω/ °C
0.003850
Interference frequency
suppression
50 Hz; 60 Hz 50 Hz
Module
Temperature unit
Degrees Centigrade, degrees Fahren‐
heit, Kelvin*
degrees
Centigrade
* only Pt 100 Standard, Ni 100 Standard, Ni 1000 Standard, LG-Ni 1000 Standard
ET 200PA SMART I/O modules
10.4 Analog input modules
ET 200PA SMART
162 Operating Instructions, 06/2019, A5E34192013-AB