EasyManuals Logo

Siemens SIMATIC ET 200PA SMART User Manual

Siemens SIMATIC ET 200PA SMART
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
Assignment planning
2
2.1 Configuration variants
Limit conditions
The IM 650 allows you to configure an ET 200PA SMART with input/output modules.
You can use the following I/O modules.
ET 200PA SMART I/O modules
All S7-300 standard I/O modules and HART analog modules that are approved for use in an
ET 200PA SMART (see the list of released modules for PCS 7 (V8.1)).
All counter modules and point-to-point couplings that are approved for use in an ET 200PA
SMART (see the list of released modules for PCS 7 (V8.1)).
You can only operate the IM 650 interface module on the integrated PROFIBUS DP interface
of a CPU 410-5H or a CPU 410 SMART with firmware version 8.1 or higher.
You may only configure an ET 200PA SMART station with active bus modules.
You can operate an ET 200PA SMART station both non-redundantly as well as redundantly:
For a non-redundant configuration, use an IM 650 on an active PS/IM bus module (6ES7650
8PA00-xAA0)
For a redundant configuration, use two IM 650 modules on an active IM/IM bus module
(6ES7650 8PB00-xAA0)
2.2 Configuring the mechanical structure
2.2.1 Horizontal or vertical configuration
Possible configurations
You can mount the ET 200PA SMART horizontally or vertically.
Always arrange the power supply and IM 650 on the left or at the bottom.
ET 200PA SMART
Operating Instructions, 06/2019, A5E34192013-AB 17

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200PA SMART and is the answer not in the manual?

Siemens SIMATIC ET 200PA SMART Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200PA SMART
CategoryControl Systems
LanguageEnglish

Related product manuals