EasyManua.ls Logo

Siemens SIMATIC ET 200PA SMART - Page 177

Siemens SIMATIC ET 200PA SMART
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
You can also use a 4-wire transducer with separate supply. This is shown in the figure below
using channel 13 as an example.
:LUH
:LUH
8Y
8Y
ADC
M
2
3
4
5
6
7
8
9
12
13
14
15
16
17
18
19
20
1
10
11
22
23
24
25
26
27
28
29
32
33
34
35
36
37
38
39
40
21
30
31
M0+
M0-
M1+
M1-
M2+
M2-
M3+
M3-
M4+
M4-
M5+
M5-
M6+
M6-
M7+
M7-
M8+
M8-
M9+
M9-
M10+
M10-
M11+
M11-
M12+
M12-
M13+
M13-
M14+
M14-
M15+
M15-
M
L+
SF
200
50
M
200
50
M
200
50
M
200
50
M
M

DC
24V
ZLUHWUDQVGXFHU
ZLUHWUDQVGXFHU
Electrical
isolaon
BUS
ASIC
+DUGZDUHVHWWLQJIRURSHUDWLRQZLWK
ZLUHWUDQVGXFHU

5HGXQGDQF\MXPSHU
Mulplexer
Mulplexer
Mulplexer
Mulplexer
Figure 10-11 AI 16 x 16 Bit with 2-wire transducer operation
Wiring and block diagrams of the AI 16 x 16 Bit with 4-wire transducer operation
When the module is used for 4-wire transducer operation, terminals 10 and 11 must not be
jumpered.
All channels of the module operate in 4-wire transducer mode in this case. Shown using
channel 9 as an example.
The parameter assignment is made via HW Config as “4WMT current”
The 4-wire transducers have a separate supply voltage.
You can also use a 2-wire transducer with separate fused supply. This is shown in the figure
below using channel 13 as an example.
ET 200PA SMART I/O modules
10.4 Analog input modules
ET 200PA SMART
Operating Instructions, 06/2019, A5E34192013-AB 177

Table of Contents

Related product manuals