Parameters/address space
4.6 Explanation of parameters
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
46 Equipment Manual, V1.0, 01/2021, A5E47073911-AA
1 The actual speed exceeds the configured speed limit during the "n+2" update interval. Due to the averaging of the
measured value, the calculated speed never exceeds the speed limit so no safe speed event is issued by the module.
Larger update times effectively filter out short speed limit violations. Therefore, if the application needs to detect
momentary speed limit violations, a shorter update time should be configured.
Speed limit
Specifies the maximum acceptable speed in velocity units for the SLS function only when
velocity is selected.
Note
The speed limit selection is disabled if "Safety Function - Limited Speed" is disabled.
Reaction to CPU STOP
Specifies whether the channel continues to count pulses while the F-CPU is in STOP mode.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals