Technical specifications
7.1 Specifications
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
84 Equipment Manual, V1.0, 01/2021, A5E47073911-AA
6ES7136-6CB00-0CA0
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1
Cat. 4, PL e
SIL acc. to IEC 61508
SIL 3
Probability of failure (for service life of 20
years and repair time of 100 hours)
Low demand mode: PFDavg in accordance with
SIL 1
2.00E-03 signal monitoring disabled
Low demand mode: PFDavg in accordance with
SIL 3
< 3.00E-05
High demand/continuous mode: PFH in accord-
ance with SIL 1
< 3.00E-08 1/h signal monitoring disabled
High demand/continuous mode: PFH in accord-
ance with SIL 3
< 1.00E-09 1/h
Ambient conditions
Ambient temperature during operation
horizontal installation, min.
0 °C
horizontal installation, max.
60 °C
vertical installation, min.
0 °C
vertical installation, max.
50 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-
altitude
On request: Ambient temperatures lower than 0
°C (without condensation) and/or installation
altitudes greater than 2 000 m
Dimensions
Width
15 mm
Height
73 mm
Depth
58 mm
Weights
Weight, approx.
42 g