Setting parameters for blocks
3.5 Programming the Ident profile
Ident profile and Ident blocks, standard function for Ident systems
102 Function Manual, 10/2018, C79000-G8976-C387-04
Table 3- 86 Command data area "TXREF" command identifier 0x08 (set Digital Out)
Address
Value
Meaning
0x0000
0x08
Command identifier "Set Digital Out"
0x0001 0x01...0x04 Number of the logical external signal. Corre-
sponds to "EXT_1", "EXT_2", "EXT_3" and
"EXT_4".
0x0002 0x00...0x02 Level of the signal
0x00: Set level statically to "low".
0x01: Set level statically to "high".
0x02: Set level for configured pulse time to
"high".
0x0003 0x01...0x07 Type of logic operation
0x01: Logical "OR"
0x02: Logical "AND"
0x03: Logical "Exclusive OR"
0x04: no logic operation
0x05: Logical "OR not"
0x06: Logical "AND not"
0x07: Logical "Exclusive OR not"
0x0004 0x00...0x05 Logical signal linked to.
If the logic operation type is 0x4, the parameter
has no significance.
0x00: Logical signal "IN_OP"
0x01: Logical signal "TRD"
0x02: Logical signal "RDY"
0x03: Logical signal "READ"
0x04: Logical signal "MATCH"
0x05: Logical signal "NOK"
0x0005 0x00 Reserved, must be 0x00 to retain upwards com-
patibility.
0x0006 0x00 Reserved, must be 0x00 to retain upwards com-
patibility.