Error messages
4.3 Errors from the communications module/reader
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
125
The carrier signal is not activated.
0xE2FE8700 There is more than one transponder in the transmission window.
General radio protocol error
0xE4FE0100 Short circuit or overload of the 24 V outputs
• The reader is using too much current.
• The reader cable is causing a short-circuit.
Possible consequences:
• The affected output is turned off
• All outputs are turned off when total overload occurs
• A reset can only be performed by turning the 24 V voltage off and on again
• and then starting "Reset_Reader"
0xE4FE0300
• Error in the connection to the reader; the reader is not answering.
– The cable between the communications module and reader is wired incorrectly or there is a cable
break
– The 24 V supply voltage is not connected or is not on or has failed briefly
– Automatic cutout on the communications module has responded
– Hardware defect
– Another reader is in the vicinity and is active
– Execute "INIT"/"WRITE-CONFIG" after correcting the error
• The antenna of the reader is turned off. A tag command to the communications module was started in
this status.
– Turn on the antenna with the command "Antenna on/off."
– The antenna is turned on (off) and has received an additional turn-on (turn-off) command
• The mode in the "SET_ANT" command is unknown
• The antenna on the reader is turned off or the antenna cable is defective
The buffer on the communications module or reader is not adequate to store the command temporarily.
The buffer on the communications module or reader is not adequate to store the data temporarily.
0xE4FE0600 The command is not permitted in this status or is not supported.
RF61xR/RF68xR: Command repetition is only possible in Presence mode.
0xE4FE0700 Startup message from reader/communications module. The reader or communications module was turned
off and has not yet received a "Reset_Reader" ("WRITE_CONFIG") command.
• Execute "INIT"
• The same physical address in the "IID_HW_CONNECT" parameter is being used more than once.
Check your "IID_HW_CONNECT" parameter assignments.
• Check connection to the reader
• The transmission speed was switched over but power has not yet been cycled
No or bad configuration data was transferred.