4.1 BACnet objects
PN/BACnet LINK
Operating Instructions, 10/2017, A5E39895543-AA
27
4.1.3
Client object references
Client object references are references to BACnet objects which are located in other BACnet
devices.
If the PN/BACnet LINK does not require any server objects, which means only client object
references are configured, the device object must still be configured.
Supported object references
The PN/BACnet LINK supports object references to the following BACnet objects:
Binary input
Binary output
Analog input
Analog output
The supported object references are defined on configuration of the PN/BACnet LINK.
When configuring, the following should be specified:
To which BACnet object on which BACnet device the client object reference in the
PN/BACnet LINK is referring to.
How access to this object is handled