Functions
4.5 Acyclic data exchange
PN/BACnet LINK
Operating Instructions, 10/2017, A5E39895543-AA
41
Error messages
If an error occurs in the PROFINET connection during an acyclic property access triggered
by a data record, then the element "PNresp" of the associated reply data record contains the
cause of the error.
Table 4- 9 PROFINET error numbers (PNresp)
Error ID
Meaning
0
No error
1
Job buffer already assigned
2
Length (Len) not sufficient for job/result
3 Incorrect data record number
4
Job buffer does not contain a result
5
Job not yet complete
In addition to the above-mentioned error messages, other errors may be reported when data
records are accessed, for example, that the specified data record is not present. These
causes of error are described in the SIMATIC S7 documentation.
If the reason for a defective property access lies on the BACnet side, then the element
"BNresp" of the associated reply data record contains a value not equal to 0. The actual
cause of the error is then described in the two elements "ErrorClass" and "ErrorCode". The
meaning of these two elements can be found in the BACnet standard.
Table 4- 10 BACnet error numbers (BNresp)
Error ID
Meaning
0
No error
!= 0
Error