Programming via Rockwell controller
9.3 Project preparation
SIMATIC RF650R/RF680R/RF685R
Configuration Manual, 03/2018, C79000-G8976-C386-06
159
5. Assign parameters for the variable as follows:
In the "Configuration" tab:
Message Type = CIP generic
Service Type = Custom
Service Code = 40
Class = 80
Instance = 1
Source Element = RF680R_001_ConfigData.Channel1.Static.buf
Destination Element = RF680R_001_ConfigData.Channel1.Static.buf
6. Select the reader for which you want to assign parameters in the "Communication" tab in
the input box "Path".
7. Select the "Connected" and "Large Connection" check boxes, if applicable.
8. Create a variable for "MSG_WRITE".
9. Assign parameters for the variable as follows:
In the "Configuration" tab:
Message Type = CIP generic
Service Type = Custom
Service Code = 41
Class = 80
Instance = 1
Source Element = RF680R_001_ConfigData.Channel1.Static.buf
10.Select the reader for which you want to assign parameters in the "Communication" tab in
the input box "Path".
11.Select the "Connected" and "Large Connection" check boxes, if applicable.
You can find more information on this subject in the section "Param_RF68xR
(Page 161)".
12.Select the relevant input word of the reader for the parameter "STATUS_WORD"
(<Readername>:I.Data[0]).
13.Select the relevant output word of the reader for the parameter "CONTROL_WORD"
(<Readername>:O.Data[0]).
14.Start the block by calling the "EXECUTE" parameter.