EasyManuals Logo

Siemens SIMATIC RF650R User Manual

Siemens SIMATIC RF650R
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #322 background imageLoading...
Page #322 background image
Appendix
A.2 Application examples of the algorithms
SIMATIC RF650R/RF680R/RF685R
322 Configuration Manual, 03/2018, C79000-G8976-C386-06
Example A - further procedure
Follow the steps below to take inventories for 10 seconds if the light barrier is interrupted.
1. Create an If condition that then always triggers the "Inventory" block when the light barrier
(input 1) is interrupted.
2. Specify the block parameters as follows;
– ATTRIBUTE = 0x80 or 0x81
– DURATION = 0x0A
– DUR_UNIT = 0x00
Example B - further procedure
Follow the steps below to take inventories if the light barrier is interrupted until the light
barrier is no longer interrupted:
1. Create an If condition that then always triggers the "Inventory" block (ATTRIBUTE =
0x86) when the light barrier (input 1) is interrupted.
2. Program the condition so that as soon as the light barrier is no longer interrupted, the
transponder data is fetched. Execute a further "Inventory" command with the following
parameters:
– ATTRIBUTE = 0x80
– DURATION = 0x00
– DUR_UNIT = 0x00
3. End the IF condition using a further "Inventory" command with the parameter
"ATTRIBUTE =0x87".
Parameter assignment - XML / OPC UA user
Follow the steps below to activate the "Smoothing" algorithm:
1. In the menu item "Settings - Read points" in the "Algorithms" area activate the
"Smoothing" algorithm and specify the values as follows:
– Observed Count: Here enter a value that guarantees reliable identification of the
transponders and at the same time ensures that transponders identified by sporadic
overshoots are sorted out. With the menu item "Diagnostics - Tag monitor" you can
determine which value is ideal here for your application.
– Lost Count: Enter the maximum value "65535" to ensure that all transponders are
identified during the specified period and are also not reported more than once. This
ensures that transponders located at the front of the palette do not leave the list of
identified transponders while the forklift truck passes the antenna and these
transponders already leave the antenna field while inventories are still being taken.

Table of Contents

Other manuals for Siemens SIMATIC RF650R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC RF650R and is the answer not in the manual?

Siemens SIMATIC RF650R Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC RF650R
CategoryOther
LanguageEnglish

Related product manuals