Control functions
7.8 Communicating with the PLC
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
265
ity when BOP, V-ASSISTANT, and USS access the same parameter at the
same time, the value of the parameter depends on the last access operation.
Configure the setup and program the PLC.
â‘¡
Configure the RS485 bus address by parameter
p29004.
The RS485 bus is used to transfer current absolute position of
the servo drive to the upper controller/PLC. You can configure
the slaver address from 1 to 31.
Select the USS communication protocol by parameter
p29007.
• p29007 = 0: no protocol
• p29007 = 1: USS protocol
• p29007 = 2: Modbus protocol
â‘£
Set the transmission baud rate by parameter p29009.
• 5: 4800 baud
• 6: 9600 baud
• 7: 19200 baud
• 8: 38400 baud
• 9: 57600 baud
• 10: 76800 baud
• 11: 93750 baud
• 12: 115200 baud
• 13: 187500 baud
Set control mode for the drive.
Save the parameters and restart the drive.
⑦
Access the parameters via USS. For IPos control mode, you can change the following parame-
ters via USS:
• p2617[0...7], p2618[0...7], p2572, p2573
For S control mode, you can change the following parameter
via USS:
• p1001 to p1007
Ten monitor parameters can be read by USS:
• r0020, r0021, r0026, r0027, r0031, r0032, r0034, r0807,
r2556, and r2521
Note
The USS protocol communication libraries of S7
-200, S7-200 SMART V1.0, and S7-
1200 do
not support the communication with the SINAMICS V90 servo drive.