EasyManua.ls Logo

Siemens SIMOTICS S-1FL6

Siemens SIMOTICS S-1FL6
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control functions
7.8 Communicating with the PLC
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
265
Note
There is no prior
ity when BOP, V-ASSISTANT, and USS access the same parameter at the
same time, the value of the parameter depends on the last access operation.
Operating steps
Main step
Sub step/comment
Configure the setup and program the PLC.
Configure the RS485 bus address by parameter
p29004.
The RS485 bus is used to transfer current absolute position of
the servo drive to the upper controller/PLC. You can configure
the slaver address from 1 to 31.
Select the USS communication protocol by parameter
p29007.
p29007 = 0: no protocol
p29007 = 1: USS protocol
p29007 = 2: Modbus protocol
Set the transmission baud rate by parameter p29009.
5: 4800 baud
6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
13: 187500 baud
Set control mode for the drive.
Save the parameters and restart the drive.
Access the parameters via USS. For IPos control mode, you can change the following parame-
ters via USS:
p2617[0...7], p2618[0...7], p2572, p2573
For S control mode, you can change the following parameter
via USS:
p1001 to p1007
Ten monitor parameters can be read by USS:
r0020, r0021, r0026, r0027, r0031, r0032, r0034, r0807,
r2556, and r2521
Note
The USS protocol communication libraries of S7
-200, S7-200 SMART V1.0, and S7-
1200 do
not support the communication with the SINAMICS V90 servo drive.

Table of Contents

Other manuals for Siemens SIMOTICS S-1FL6

Related product manuals