Tuning
9.3 One-button auto tuning
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
319
↓
...
If the dynamic factor setting cannot be increased up to the desired level because of machine
resonance beyond 250 Hz, the function of resonance suppression can be used to suppress
machine resonance and thus increase dynamic factor. Refer to Section "Resonance
suppression (Page 326)" for detailed information about the function of resonance
suppression.
Note
The tuning configuration parameters must be set carefully when the auto tuning function is
disabled (p29021=0).
After servo on, the motor will run with the test signal.
-button auto tuning process completes successfully, parameter p29021 will be
set to 0 automatically. You can also set the parameter p29021 to 0 before servo on to
interrupt the one
-button tuning process. Before you save the parameters on the drive, make
sure that p29021 has changed to 0.
-button auto tuning proc
ess completes successfully, bit 0 of parameter p29300
will be set to 0 automatically or remain unchanged (= 0), which means the drive is in "S OFF"
state.
Note
Do not use the JOG function when you use the one
-button tuning function.
one-
button tuning is activated, no operation will be allowed except the servo off and
quick stop with the digital input EMGS.
With one-button auto tuning, the servo drive can automatically estimate the ratio of load
moment of inertia and set the following relevant parameters accordingly.
Speed setpoint filter activation
Speed setpoint filter 1 type
Speed setpoint filter 1 denominator natural
frequency
Speed setpoint filter 1 denominator damping
Speed setpoint filter 1 numerator natural
frequency
Speed setpoint filter 1 numerator damping
Actual speed smoothing time
Activates current setpoint filter
Current setpoint filter 1 denominator natural
frequency
Current setpoint filter 1 denominator damping