Tuning
9.6 Resonance suppression
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
327
Using the resonance suppression function
Note
The resonance suppression fun
ction is used together with the auto tuning function. In real-
time auto tuning and one
-button auto tuning mode, the function is activated by default.
When you use real
-time auto tuning function, you are recommended to disable the
resonance suppression func
tion to get a high dynamic performance if there is no resonance
in the machine.
The function can be activated/deactivated with the following parameters:
For one-button auto tuning: bit 1 of p29023
For real-time auto tuning: bit 6 of p29024
Resonance suppression with one-button auto tuning (p29021=1, p29023.1=1)
Before you use the resonance suppression function with one-button auto tuning, make sure
the load is mounted as required and the servo motor can rotate freely. When the one-button
auto tuning process completes successfully, the servo drive automatically sets the following
notch filter relevant parameters with real machine characteristic. Four current setpoint filters
can be activated at most.
Parameter
Range
Default
Unit
Description
p1663 0.5 to 16000 1000 Hz Natural frequency of current notch filter 2
denominator.
p1664
0.001 to 10
0.3
-
Damp of current notch filter 2 denominator.
p1665 0.5 to 16000 1000 Hz Natural frequency of current notch filter 2
numerator.
p1666
0.0 to 10
0.01
-
Damp of current notch filter 2 numerator.
p1668 0.5 to 16000 1000 Hz Natural frequency of current notch filter 3
denominator.
p1669
0.001 to 10
0.3
-
Damp of current notch filter 3 denominator.
p1670 0.5 to 16000 1000 Hz Natural frequency of current notch filter 3
numerator.
p1671
0.0 to 10
0.01
-
Damp of current notch filter 3 numerator.
p1673 0.5 to 16000 1000 Hz Natural frequency of current notch filter 4
denominator.
p1674
0.001 to 10
0.3
-
Damp of current notch filter 4 denominator.
p1675 0.5 to 16000 1000 Hz Natural frequency of current notch filter 4
numerator.
p1676
0.0 to 10
0.01
-
Damp of current notch filter 4 numerator.
Note
Notch filter remains active when the resonance suppression function is activated
automatically.
After one
-button tuning is completed, four filters can be activated at most. You can
deactivate the notch filters by setting the parameter p1656.