Diagnostics
11.2 List of faults and alarms
SINAMICS V90, SIMOTICS S-1FL6
406 Operating Instructions, 04/2019, A5E36037884-007
Alarm
Cause
Remedy
A7480: EPOS: Software limit
switch plus reached
The axis is at the position of the software
limit switch plus. An active traversing block
was interrupted.
Correct the target position.
Change software limit switch plus (CI:
p2581).
A7496: SON enable missing
In the IPos control mode or a com-
pound control mode with IPos, no ser-
vo on command is sent to the drive via
Modbus when p29008 = 1.
In the IPos control mode, rising edge is
triggered for the P-TRG signal when
the drive is in servo off status.
In the PTI control mode, any faults
which is caused by implementing the
"Enable trial run" operation with the V-
ASSISTANT lead to A7496.
Send servo on command to the drive via
Modbus
Set the drive to servo on status firstly and
trigger a rising edge for the P-TRG signal.
Acknowledge the faults firstly and imple-
ment "Enable trial run" again.
A7576: Encoderless opera-
tion due to a fault active
Encoderless operation is active due to a
fault.
Remove the cause of a possible encoder
fault.
Carry out a POWER ON (power off/on) for
all components.
A7582: Position actual value
preprocessing error
An error has occurred during the position
actual value preprocessing.
Check the encoder for the position actual
value preprocessing.
Refer to F52931.
A7585: P-TRG or CLR active
In the PTI mode or a compound mode with
PTI, the P-TRG or CLR function is activat-
ed.
In the PTI mode, deactivate the P-TRG or
CLR function; in the compound mode with
PTI, do not switch to other modes.
A7588: Encoder 2: Position
value preprocessing does not
have a valid encoder
The parameter configuration of PTI coun-
ter is incorrect.
Default the drive and re-configure the param-
eters.
A7805: Power unit overload
I
2
t
Alarm threshold for I
2
t overload of the
power unit exceeded.
Reduce the continuous load.
Adapt the load duty cycle.
Check the assignment of the rated cur-
rents of the motor and motor module.
A7965: Save required
The angular commutation offset was re-
defined and has still not been saved.
In order to permanently accept the new
value, it must be saved in a non-volatile
fashion.
This alarm automatically disappears after the
data has been saved.