Diagnostics
11.2 List of faults and alarms
SINAMICS V90, SIMOTICS S-1FL6
406 Operating Instructions, 04/2019, A5E36037884-007
A7480: EPOS: Software limit
switch plus reached
The axis is at the position of the software
limit switch plus. An active traversing block
was interrupted.
• Correct the target position.
• Change software limit switch plus (CI:
p2581).
A7496: SON enable missing
• In the IPos control mode or a com-
pound control mode with IPos, no ser-
vo on command is sent to the drive via
Modbus when p29008 = 1.
• In the IPos control mode, rising edge is
triggered for the P-TRG signal when
the drive is in servo off status.
• In the PTI control mode, any faults
which is caused by implementing the
"Enable trial run" operation with the V-
ASSISTANT lead to A7496.
• Send servo on command to the drive via
Modbus
• Set the drive to servo on status firstly and
trigger a rising edge for the P-TRG signal.
• Acknowledge the faults firstly and imple-
ment "Enable trial run" again.
A7576: Encoderless opera-
tion due to a fault active
Encoderless operation is active due to a
fault.
• Remove the cause of a possible encoder
fault.
• Carry out a POWER ON (power off/on) for
all components.
A7582: Position actual value
preprocessing error
An error has occurred during the position
actual value preprocessing.
Check the encoder for the position actual
value preprocessing.
Refer to F52931.
A7585: P-TRG or CLR active
In the PTI mode or a compound mode with
PTI, the P-TRG or CLR function is activat-
In the PTI mode, deactivate the P-TRG or
CLR function; in the compound mode with
PTI, do not switch to other modes.
A7588: Encoder 2: Position
value preprocessing does not
have a valid encoder
The parameter configuration of PTI coun-
ter is incorrect.
Default the drive and re-configure the param-
eters.
A7805: Power unit overload
I
2
Alarm threshold for I
2
t overload of the
power unit exceeded.
• Reduce the continuous load.
• Adapt the load duty cycle.
• Check the assignment of the rated cur-
rents of the motor and motor module.
The angular commutation offset was re-
defined and has still not been saved.
In order to permanently accept the new
value, it must be saved in a non-volatile
This alarm automatically disappears after the
data has been saved.