Start-Up 02.2001 SLE / SLE-DP – SIMOLINK Encoder
GWE-477 763 4070.76 J Siemens AG
6-2 Operating Instructions SIMOVERT MASTERDRIVES
6.1 DIL switch settings
The DIL switch settings apply to both models of SIMOLINK Encoder.
Special features of the SLE-DP encoder are described in Section 6.4.
1
1
1
0
0
0
S1
S2
S3
READ
ADDRESS
SLE
ADDRESS
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
0
2
1
2
2
READ
CHANNEL
SLE active
PPR
Fig. 6-1 Layout of DIL switches on right-hand side panel of SLE / SLE-DP
Illustrated settings:
Read channel = 3, SLE active, number of pulses = 4096 pulses/rev, read
address = 0, SLE address = 60