SLE / SLE-DP – SIMOLINK Encoder 02.2001 Start-Up
Siemens AG GWE-477 763 4070.76 J
SIMOVERT MASTERDRIVES Operating Instructions 6-13
6.4.2 PROFIBUS station address
A station address between 1 and 99 can be allocated via two BCD
rotary switches on top of the SLE-DP housing. Changing the station
address via PROFIBUS is not supported (SET_SLAVE_ADRESS see
above).
DP-SLAVE-
ADDRESS
UNITS
TENS
ERROR
0
1
2
3
4
5
9
7
6
8
0
1
2
3
4
5
9
7
6
8
Fig. 6-6 SLE-DP; BCD rotary switch for station address
(illustrated setting: Station address = 47)
Switch Designation Meaning Range
DP-SLAVE-ADDRESS PROFIBUS-DP station address
= 10 *
TENS
+
UNITS
1…99
0
1
2
3
4
5
9
7
6
8
UNITS Units digit of PROFIBUS station address 0…9
0
1
2
3
4
5
9
7
6
8
TENS Tens digit of PROFIBUS station address 0…9
UNITS rotary switch is the rear switch on the housing top panel (see plan view).
Table 6-10 SLE-DP; BCD rotary switches
The possible setting of the BCD rotary switches to station address 0 is
converted internally to a station address of 126.
NOTICE