To activate the safety functions, proceed as follows:
1. Select the "Copy parameter" button.
2. Press the "Activate settings" button.
3. To save the data in the inverter, click the "Copy RAM to ROM" button: .
4. Go offline: .
5. Switch off the inverter power supply.
6. Wait until all LEDs on the inverter go off.
7. Switch on the inverter power supply again. Your settings only become effective after this
power-on reset.
You have transferred the settings from the PG to the inverter with STARTER and activated
the safety functions.
Procedure with Startdrive when the safety functions are enabled
To transfer the settings from the PG to the inverter with Startdrive and activate the safety
functions, proceed as follows:
1. Save the project.
2. Select "Load to device."
Figure 7-1 Activating settings in Startdrive
3. Connect Startdrive online with the drive.
4. Click the "Start safety commissioning" button.
Saving settings and series commissioning
7.2 Saving the settings to a PC
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 335