5. Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6. Click the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the inverter supply voltage.
10.Wait until all LEDs on the inverter go dark (no voltage condition).
11.Switch on the inverter supply voltage again.
You have transferred the settings from the PG to the inverter with Startdrive and have activated
the safety functions.
Saving settings and series commissioning
7.2 Saving the settings to a PC
SINAMICS G120C converter
336 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF